CS450/CS455 Pressure Transducer
;{CR10X}
;
*Table 1 Program
01: 60 Execution Interval (seconds)
1: SDI-12 Recorder (P105)
1: 0 SDI-12 Address
2: 0 Start Measurement (aM0!)
3: 1 Port ;this is where the white wire is connected
4: 1 Loc[Data_1 ]
5: 1.0 Mult
6: 0.0 Offset
*Table 2 Program
02: 0.000 Execution Interval (seconds)
*Table 3 Subroutines
End Program
After Instruction 105 is executed, the input location called “Data_1” will hold
the measured pressure, reported in PSI, and the input location called Data_2
will hold the measured temperature, in degrees Celsius. The results can be
further processed by the logger. Note that Port 1 specifies that the SDI-12 data
line is to be connected to the Port C1.
7. Maintenance
Campbell Scientific recommends that the CS450/CS455 be factory recalibrated
and check every 24 months. Before a CS450/CS455 sensor is sent to Campbell
Scientific, the customer must get an RMA (returned material authorization)
and fill out the Declaration of Hazardous Material and Decontamination form.
The CS450/CS455 has no user-serviceable parts. Cable can be damaged by
abrasion, rodents, sharp objects, twisting, crimping or crushing and pulling.
Take care during installation and use to avoid cable damage. If a section of
cable is damaged, it is recommended that you send your sensor back to replace
the bale harness assembly.
Periodic evaluation of the desiccant is vital for keeping the vent tube dry. The
CS450/CS455 ships with the desiccant tube attached. To assess the
effectiveness of the desiccant, use on of the following:
The desiccant in the tube changes color from blue to pink when the drying
power is lost.
An enclosure humidity indicator such as CSI PN6571 humidity indicator
card.