TLX106 WEATHER STATIONINSTRUCTION MANUAL3/01COPYRIGHT (c) 1993-2001 CAMPBELL SCIENTIFIC, INC.
Section 1. Preparation and Siting1-21.2.1 Tools for Tower InstallationAll TowersShovelRakeOpen end wrenches: 3/8", 7/16", ½", (2) 9/1
Section 1. Preparation and Siting1-31.2.3 Supplies for Power and Communications OptionsAC PowerWire, conduit, and junction boxes as neededPhone Mode
Section 1. Preparation and Siting1-4Situations to avoid include:• large industrial heat sources• rooftops• steep slopes• sheltered hollows• high
Section 1. Preparation and Siting1-5(Section 1.4.1). A general map showing magnetic declination for the contiguousUnited States is shown in Figure 1
Section 1. Preparation and Siting1-6Telephone numbers:Phone Number Baud Rates303-273-8672 2400303-273-8673 1200303-273-8678 1200Upon carrier-signal d
Section 1. Preparation and Siting1-7Exiting:Press "Cntrl-Z" to exit GEOMAG.When the main menu reappears either select another option or typ
Section 1. Preparation and Siting1-8FIGURE 1.4-3. Declination Angles West of True North Are Added to 0to Get True North
2-1Section 2. TLX106 Tower InstallationDo not install near power lines. If any part of the towercomes in contact with power lines you could beKILLED
Section 2. TLX106 Tower Installation2-22.1 Base Installation2.1.1 Supplied Components(3) ½ inch L-Bolts(9) ½ inch Nuts(1) Anchor TemplateRefer to S
Section 2. TLX106 Tower Installation2-3D TO O OLTOO T DLLTTLTOTO FIGURE 2.1-2. TLX106 Tower Base Installation2.2 Tower Installation2.2.1 Supplied
This is a blank page.
Section 2. TLX106 Tower Installation2-44. Cut and save a 9 inch piece of 12 AWG ground wire from the 12 footlength provided. Thread the remaining 1
Section 2. TLX106 Tower Installation2-52.3.2 Grounding ProcedureGround the tower as shown in Figure 2.2-1.1. Place the ground rod clamp on the rod.
This is a blank page.
3-1Section 3. TLX106 InstrumentationInstallationThe weather station datalogger, power supply, sensor connection panel, communicationsdevices, and dat
Section 3. TLX106 Instrumentation Installation3-23.1 Enclosure, Datalogger, Power Supply3.1.1 Battery Option InstallationSFIGURE 3.1-1. Rechargeab
Section 3. TLX106 Instrumentation Installation3-3The solar panel should be oriented to receive maximum insolation overthe course of the year. Sugges
Section 3. TLX106 Instrumentation Installation3-4ORTH FIGURE 3.1-3. Mounting and Grounding the TLX106 Enclosurec) Slide the enclosure to the top of
Section 3. TLX106 Instrumentation Installation3-5EarthGroundStand offConnector#4SensorsTEMPCS615TEMPRAIN(PRECIP)TEMP / RHSOLARRADIATIONCOMMWS/WDSDI 1
Section 3. TLX106 Instrumentation Installation3-6If you received a telecommunications kit separate from the TLX106 Enclosure,follow the "Interna
Section 3. TLX106 Instrumentation Installation3-73.3.1.2 External InstallationThe following modem kit components are used to make the externalconnec
Warranty and AssistanceThe TLX106 WEATHER STATION is warranted by CAMPBELLSCIENTIFIC, INC. to be free from defects in materials and workmanshipunder n
Section 3. TLX106 Instrumentation Installation3-83. Connect the SC932C 9-pin port to the internal TLX106 Enclosure 9-pinport with the blue ribbon cab
Section 3. TLX106 Instrumentation Installation3-9- RCV (white)- RCV (black)+ RCV (green)+ RCV (red)+ XMT (red)+ XMT (green)- XMT (black)- XMT (white)
Section 3. TLX106 Instrumentation Installation3-10DO NOT EATUNITED DESICCANTS-GATES101CHRISTINE, BELEN, NEW MEXICO 87002DESI PAKSPECIFICATION MIL-D-3
4-1Section 4. TLX106 Sensor ArmInstallation4.1 Components(1) TLX106 Sensor Arm(1) Met One 034A Wind Sensor(1) 034A Mounting Shaft(1) Radiation Shiel
Section 4. TLX106 Sensor Arm Installation4-24.3 Sensor ConnectionRefer to Section 3 for sensor connection details.4.4 034A Wind Sensor Installation
Section 4. TLX106 Sensor Arm Installation4-34.5 RH and Temperature Radiation ShieldMount the radiation shield to the sensor arm as shown in Figure 4
Section 4. TLX106 Sensor Arm Installation4-4InputLocation ParameterNormal Range1 Enclosure Close to airTemperature (°C) temperature3 Solar Radiation
Section 4. TLX106 Sensor Arm Installation4-5123456Air Temperature andRelative HumiditySensorConnectorPinDataloggerRelative Humidity (0-1VDC)Air Tempe
Section 4. TLX106 Sensor Arm Installation4-6Solar RadiationSensor40.2 - 90.2 OHMConnectorPinDatalogger132Not UsedNot UsedNot Used3 H3 LGShield4561234
5-1Section 5. Software Installation andSettings5.1 Measure Sensors and Process DataA pre-written datalogger program (PN 14079) comes installed in th
This is a blank page.
Section 5. Software Installation and Settings5-2Here again the Communications Enabled button must be selected. Thenselect the proper Modem Type and
Section 5. Software Installation and Settings5-3The final termination must be to a CR10X-TD logger. The Proline willdefault to work with a logger na
Section 5. Software Installation and Settings5-4If not already started, start the LoggerNet server by double clicking theblue icon. Then start the C
Section 5. Software Installation and Settings5-5“Keep Logger On Line” This is used to force LoggerNet to stayconnected to the station the entire time
Section 5. Software Installation and Settings5-6Now reopen Net Admin and go to the logger previously set up. Nowwe will check to see if the Table De
Section 5. Software Installation and Settings5-75.3 Create MessagePerform the following steps using the Message Editor provided inProLine Software:1
Section 5. Software Installation and Settings5-8FIGURE 5.3-2. The available options provided by the source menu are shown.FIGURE 5.3-3. When the we
6-1Section 6. Maintenance andTroubleshootingThese guidelines apply to several Campbell Scientific weather stations.6.1 MaintenanceProper maintenance
Section 6. Maintenance and Troubleshooting6-26.1.4 Sensor MaintenanceSensor maintenance should be performed at regular intervals, depending on thede
Section 6. Maintenance and Troubleshooting6-32. Punch a very small hole in the bottom of the can.3. Place the can in the top funnel of the rain gage
iTLX106 Weather StationTable of Contents1. Preparation and Siting1.1 Installation Tasks ...
Section 6. Maintenance and Troubleshooting6-4At the computer:D. Make sure the Station File is configured correctly.E. Check the cable(s) between the
TLX106 Weather Station Table of Contentsii4.6 Pyranometer ...4
TLX106 Weather Station Table of Contentsiii5.3-1 ProLine software provides an easy-to-use message editor ...5-75.3-2 The available opti
This is a blank page.
1-1Section 1. Preparation and SitingThese guidelines apply to several Campbell Scientific weather stations.1.1 Installation tasks1.1.1 Indoors• Im