CS106 Barometric Pressure Sensor
Supply Voltage Control: When enabled with an internal jumper, the CS106 is
on continually. When disabled, the CS106 can be turned on/off with
5 VDC/0 VDC.
Supply Voltage Sensitivity: negligible
Current Consumption: <4 mA (active); <1 μA (quiescent)
Output Voltage: 0 to 2.5 VDC
Warm Up Time: 1 second
Pressure Fitting: barbed fitting for 1/8” I.D. tubing
Overpressure Limit: 2000 mb
The black outer jacket of the cable is Santoprene
®
rubber. This
compound was chosen for its resistance to temperature extremes,
moisture, and UV degradation. However, this jacket will
support combustion in air. It is rated as slow burning when
tested according to U.L. 94 H.B. and will pass FMVSS302.
Local fire codes may preclude its use inside buildings.
NOTE
3. Installation and Wiring
3.1 Jumper Settings
The CS106 can be operated in one of two modes: shutdown and normal. The
mode is selected by a jumper located underneath the plastic cover of the
barometer. When the jumper is not installed, the CS106 is in shutdown mode
and the datalogger turns the CS106 on and off with a control port or excitation
channel; to use the excitation channel the datalogger must be able to provide an
excitation voltage of 5 VDC. When the jumper is installed the CS106 is in
normal mode and powered continuously.
CS106s shipped from Campbell Scientific are configured for
shutdown mode (jumper open).
NOTE
The location of the jumper is shown in Figure 3-1.