Model HFP01SC Self-Calibrating Soil Heat Flux Plate
;{CR23X}
;
*Table 1 Program
01: 1 Execution Interval (seconds)
;Measure HFP01SC on smaller range.
;
1: Volt (Diff) (P2)
1: 1 Reps
2: 21 10 mV, 60 Hz Reject, Slow Range
3: 9 DIFF Channel
4: 2 Loc [ shf_mV ]
5: 1 Mult
6: 0 Offset
;Measure HFP01SC on larger range.
;
2: Volt (Diff) (P2)
1: 1 Reps
2: 25 5000 mV, 60 Hz Reject, Fast Range
3: 9 DIFF Channel
4: 8 Loc [ shf_mV_a ]
5: 1 Mult
6: 0 Offset
;Load in the factory calibration.
;
3: If (X<=>F) (P89)
1: 3 X Loc [ cal ]
2: 1 =
3: 0 F
4: 30 Then Do
;Factory calibration in W/(m^2 mV) = 1000/sensitivity.
;
4: Z=F (P30)
1: 1 F ; <- Enter the unique calibration here
2: 0 Exponent of 10
3: 3 Z Loc [ cal ]
5: End (P95)
;Use data from the larger measurement range.
;
6: If (X<=>F) (P89)
1: 2 X Loc [ shf_mV ]
2: 4 <
3: -99990 F
4: 30 Then Do
7: Z=X (P31)
1: 8 X Loc [ shf_mV_a ]
2: 2 Z Loc [ shf_mV ]
8: End (P95)