APPENDIX G. CALLBACK (CR23X INITIATED TELECOMMUNICATIONS)
G-8
9: Thermocouple Temp (DIFF) (P14)
1: 1 Reps
2: 11 10 mV, Fast Range
3: 5 DIFF Channel
4: 1 Type T (Copper-Constantan)
5: 1 Ref Temp (Deg. C) Loc [ RefTemp ]
6: 2 Loc [ TempDegC ]
7: 1.0 Mult
8: 0 Offset
;*************************************************
;If the error location has been incremented to 1 (CR23X
;has called pager twice), set Flag 4 high to disable page.
;*************************************************
10: IF (X<=>F) (P89)
1: 4 X Loc [ ErrorLoc ]
2: 1 =
3: 1 F
4: 14 Set Flag 4 High
11: If Flag/Port (P91)
1: 14 Do if Flag 4 is High
2: 30 Then Do
12: Z=F (P30)
1: 0 F
2: 0 Exponent of 10
3: 4 Z Loc [ ErrorLoc ]
13: Z=F (P30)
1: 1 F
2: 0 Exponent of 10
3: 5 Z Loc [ new_flag ]
14: End (P95)
;*********************************************
;Flag 8 is used as a page system override. If flag 8
;is high, the CR23X will not call the pager. This allows
;for the use of a timer to prevent call out after the
; initial attempt is made for a specified length of time.
;*********************************************
;
;*********************************************
;Old_flag / new_flag are used to catch the transition
;from a call out condition to a reset the flag condition.
;*********************************************
15: IF (X<=>F) (P89)
1: 6 X Loc [ old_flag ]
2: 1 =
3: 0 F
4: 30 Then Do