Przeglądanie stron 359
Section 12. Program Control Instructions
12-16
Result Location
Result Code Description
-1001 The attempted setting is a read-only setting
-1002 Out of space in the remote
-1003 Syntax error
0 Success
>1 Number of communication failures
Routing Table Information (P199)
A program control instruction that is used to store the datalogger's routing table
information in a series of input locations. This instruction is used most often as
a trouble-shooting tool.
10: PakBus - Routing Table Information (P199)
1: 0000 First Loc [ ______________ ]
Parameter 1 specifies the first input location in which to begin storing the
inf
or
mation. For each route, there are 3 pieces of information returned:
1. The PakBus Address of the Destination datalogger.
2. The PakBus address of any datalogger used as a hop to the Destination
datalogger.
3. The Response Metric, in seconds (each hop takes 1 second).
A -1 in an input location indicates the end of the routing table information.
Note: The input locations required for this instruction must be allocated
ma
nual
ly.
Example
Consider the following routing table information:
Master Datalogger
PakBus Addr 3
PakBus Addr 4 PakBus Addr 5