Section 9. Program Control Instructions
SlowSequence Example
'CR800 Series Datalogger
'Slow Sequence Example
Public Temp107, PanelT, BattVolts
DataTable (T107,True,-1)
DataInterval (0,1,Min,10)
Average (1,Temp107,FP2,False)
EndTable
BeginProg
Scan (1,Sec,10,0)
Therm107 (Temp107,1,1,Vx1,0,250,1.0,0)
CallTable T107
NextScan
'First Slow Sequence Scans once a minute and stores hourly average
SlowSequence
DataTable (TPanel,True,-1)
DataInterval (0,1,Hr,10)
Average (1,PanelT,FP2,False)
EndTable
Scan (1,Min,3,0)
PanelTemp (PanelT,250)
CallTable TPanel
NextScan
'Second Slow Sequence Scans every 30 minutes and stores daily average and min.
SlowSequence
DataTable (BattV,True,-1)
DataInterval (0,1,Day,10)
Average (1,BattVolts,FP2,False)
Minimum (1,BattVolts,FP2,False,False)
EndTable
Scan (30,Min,3,0)
Battery (BattVolts)
CallTable BattV
NextScan
EndProg