Section 14. PakBus Networking
14-4
Beaconing CR800_20 is discovered by the router neighbor filter. There is no need for
the leaf node to beacon. To minimize rf traffic, keep beaconing off (at 0):
Baud Rate SDC7 Not user configurable (see Network Configuration Basics, Communication
Peripheral Setup, Baud Rates).
Example Network – Configuration of RF401s
Setup Description
General If RF401 settings have changed from factory defaults, use Device
Configuration Utility to set factory defaults, and then proceed with setups
below.
Active Interface
(Port)
Use Device Configuration Utility for setup.
Base RF401: Set to AutoSense.
Remote RF401s: Set to CSDC 7.
Note: In PakBus networks a CSDC 7 (or CSDC 8) port is more efficient
than the default Modem Enable (ME) port.
RS-232 Baud
Rate
Base (PC) RF401: Set to 38400 baud matching LoggerNet Setup.
Remote RF401s: default (9600 baud)
Hopping
Sequence
Set all RF401s to 1.
Network Address Set all RF401s to 2.
Radio Address Not used with PakBus Aware protocol (all RF401s at 0).
Retry Level Set all RF401s to Medium.
Protocol Set all RF401s to PakBus Aware.
Standby Mode Set all RF401s to “<24 mA, Always on, no long header”.
After completing the above configurations, serial cable the AutoSense RF401
(connect AC adapter) to the PC COM port configured in the LoggerNet device
map. Connect the other RF401s to CR800_10 and CR800_20. Run
LoggerNet and use Connect Screen to connect to CR800_10. It may take a
few seconds to connect. Run PakBus Graph and you should soon see this
configuration: